VA-96-H

Panel meter VAW AC

Panel meter VAW AC – VA – 96/H

Parameter: Voltage, Current, Active Power, Power Factor (PF), Apparent Power & Frequency.
True RMS Measurement of all parameters.
CT Primary Selection Up to 400 (For secondary 5A)
User can set the Display in Auto Scrolling or fixed screen mode via front panel key

  • 3 Line display, 7 Segment LED Display
  • 7 + parameter with LED indication
  • CT Selectable up to 2000/5 or 1amps
  • RS-485 MODBUS Communication
Availability: Available on backorder
Model VA-96/H
Over All Size 96*96*42 mm
Cut Out 92*92 mm
Mounting Type Panel Mounting
I/P Supply 230VAC,+/-10%,50Hz.(Other Supply on Request)
Timing Range 999.9/99.99/9999 sec/Min/Hr (selectable)
Display Method Upper = 3 line 4 digit/line 0.56” RED or White 7-Segment LED display.for PV
Input 5A AC Direct
Active Power 0.000 – 9999 W
Active Energy ( kWH) 0.000 – 999999 kWh
Power Factor ( PF ) 0.10 – 1.000 PF
Apparent Power ( VA ) 0.000 – 9999 VA
Frequency ( Freq ) 45 to 65 Hz
CT Ratio 10mA to 400/5 CT Selectable
Voltage 20 to 300V
Accuracy class 0.5
Time Setting Front Key Pad.
Operating Mode On delay,Off delay,Forward,Reverse,Cyclic,(selectable)
Count Direction UP or Down Selectable
Power Fail Memory Yes/ NO Selectable
Start Logic Power ON / Front Key/External Dry Contact/NPN-PNP Proximity S/W.
Reset Front Key, Power interruption.or External start pulse.
Control O/P 1 C/O/ 2 C/O-Relay o/p (5A@230vac) or Isolated SSR o\p (+12vdc)
LED Indication Relay status.
EMC Standard EN50081-2 & EN 50082-2 Generic Stds for Industrial Environment
Safety Standards Meets EN61010, Installation Catagory II
Operating Ambient 0’C to 55’C
Storage Temperature -10 to +50 °C
Operating Humidity 5~95%RH Non-condensing