| Model | LC-DIN-2Z |
| Over All Size | 70*60*112 mm |
| Mounting Type | Wall Mounting |
| I/P Supply Voltage | +24VDC or 230VAC,50 Hz,+/-15%, |
| Perfomance | a) Excitation Voltage : 5 VDC fixed,short circuit proof. |
| b) Load Current : 150mA Max. | |
| c) Coversion Rate : 50 samples /seconds. | |
| d) Filtering : By Digital Signal Processing. | |
| e) A/D converter : High Spped 20 Bit delta-sigma. | |
| f) ADC Resolution : 80000 counts | |
| g) Sensitivity : 0.02micro volt/count. | |
| h) Linearity : <0.01% of F.S /’C | |
| i) Signal I/P Range : -0.5mv/V to 3.5mV/V | |
| j) Weighing Range : 999.999 /9999.99/99999.9/999999 Kg.(Selectable) | |
| l) Calibration Method One touch by key pads. | |
| Analog I/P | 2-Load cell I/P |
| Analog O/P | 0-10VDC or 4-20mA (Factory set) |
| Comm.O/P | MOBUS RTU (RS485) |
| EMC Standard | EN50081-2 & EN 50082-2 Generic Stds for Industrial Environment |
| Safety Standards | Meets EN61010, Installation Catagory II |
| Operating Ambient | 0’C to 55’C |
| Storage Temperature | -10 to +70 °C |
| Operating Humidity | 5~80%RH Non-condensing |