LCD Based Single CH-Auto Clave Controller
- Temperature Input: RTD Pt100
- Programmable Sterilization Timer with Guaranteed Soak Time
- High-Temperature Safety Alarm
- Computed Saturated Steam Pressure Display
- Independent Purging and Sterilization Set-points
- Independent Outputs for Air Valve & Steam Control
- Front Key for Sterilization Cycle Reset & Start Command
- Water Level Low Switch Input
- DIN Standard Dimensions: 96(H) X 96(W) X 55(D), mm”
- Specification
- Download
Model | PUR-9D |
Display | |
Display Method | 16×2 Line Alphanumeric LCD |
OutPut Indication | 3 Red LEDs (3mm ) Heater/Air Valve/Alarm |
Keys | |
Type | 4+1 Tactile Switches |
Functions | ON/OFF, SET, DOWN, UP, ENTER |
Sensor Input | |
Type | RTD (Pt100), 3 wire |
Display Range | 000.0 to 150.0’C |
Display Resolution | 0.1’C |
Accuracy | ± 0.25% of reading ± 1°C |
Sterilization Timer | |
Operation Mode | Soak Time at Sterilization Setpoint with Hold Band |
Range | 1 to 999 Minutes |
Power-fail Recovery | Resume, Reset, Abort |
Sterilization Control | |
Type | ON-OFF |
Mode | Heat Control |
Control Parameters | Sterilization Setpoint, Hysteresis |
Output (OP-1) | Relay Change-over Contacts or SSR Drive ( Factory Set) |
Air Purging Control | |
Control Type | ON-OFF |
Control Parameters | Air Outlet Setpoint |
Output (OP-2) | Relay Change-over Contacts or SSR Drive ( Factory Set) |
Alarms | |
Functions | High-Temperature Deviation, End-of-Sterilization, Low Water Level |
Output (OP-3) | Relay Change-over Contacts |
Outputs | |
Relay | Contact Type : Potential-free Change-over Contacts Contact Rating : 3A Resistive @ 120/240 Vac Contact Life : > 5,00,000 Operations at Rated Voltage / Current |
Power Supply | |
Type | Linear PSU |
Line Voltage | 230VAC, 50/60Hz Optional: 18~36 VDC |
Consumption | 5VA Max |
Physical | |
Mounting | Plug-in with Panel Mounting Clamps |
Overall Dimensions | 96(H) X 96(W) X 55(D), mm |
Panel Cutout | 92(H) X 92(W), mm |
Environmental | |
Operating Ambient | 0’C to 55’C |
Storage Temperature | -10 to +70 °C |
Operating Humidity | 5~80%RH Non-condensing |
EMC Standard | EN50081-2 & EN 50082-2 Generic Stds for Industrial Environment |
Safety Standards | Meets EN61010, Installation Catagory II |