Hot

Universal T/C I/P- PID Controller With Amp.Meter.

Universal T/C I/P Dual Display 2-Set Point PID Controller With Amp.Meter.

Availability: Available on backorder
MODEL PID-4C
Over All Size 48*48*90 mm
Cut Out Size 44*44 mm
Mounting Type  Panel Mounting.
I/P Supply 230VAC,+/-15%,50Hz.  ( Others on request)
I/P Sensor a)  J,K,for T/C  (Field Selectable)
 b)  CT for Heater Load.(50Amp Max)
Display Method Upper Right : 3-Digit 0.29″ RED 7 Segment LED Display for Temp.PV
 Upper Left: 3-Digit 0.29″ GREEN 7 Segment LED Display for Heater Load PV
 Lower : 3-Digit 0.29″ GREEN 7 Segment LED Display Heater SV
Range a) J-T/C= 600’C…
 b) K-T/C=950’C
 c) 0.5 to 50.0 Amp for Heater Load.
Indication Accuracy 0.25% of FSR or 1’C Max, Software Calibrated Lineariser.
Control Accuracy +/-1’C of Set value.
Resolution a) 1’C for Temperature
 b) 0.1 Amp for Load Current.
CJC  Automatic Cold Junction compensation for TC.
Setting Method By Front Keypad
Control O/PRelay-1- 1 C/O-Relay o/p (3A@230vac) or Isolated SSR o\p (+12vdc) for Heater.
Relay-2- 1 C/O-Relay o/p (3A@230vac) for Blower.
Control Method Control-1 -Auto-Tune PID or ON/OFF (Field Selectable)
 Control-2 -ON/OFF
Setpoint-1Main SetPoint
Setpoint-2Heating + Heating, Heating + Cooling ,Heating + High /Low Alarm.
Sensor Break Protection Relay OFF when the sensor breaks.
OutPut IndicationLED Indication on the front panel for Each O/P status.
EMC Standard EN50081-2 & EN 50082-2 Generic Stds for Industrial Environment
Safety Standards Meets EN61010, Installation Catagory II
Operating Ambient0’C to 55’C
Storage Temperature-10 to +70 °C
Operating Humidity5~80%RH Non-condensing

 

Download PDF File